Technical Specifications |
Insulator type |
ANSI |
52-11 |
Minimum mechanical failing load |
kN |
222 |
Minimum mechanical residual strength |
kN |
133 |
Testing single impact force |
ะยทะผ |
45 |
Diameter of the insulating part, D |
mm |
280 |
Spacing, H |
mm |
170 |
Nominal creepage distance |
mm |
380 |
Ball and socket coupling, d (IEC 60120) |
- |
type K |
Puncture voltage in insulating medium |
kV |
130 |
50 Hz withstand voltage (dry) |
kV |
80 |
50 Hz withstand voltage (wet) |
kV |
50 |
Dry lightning impulse withstand voltage 1.2/50 (+/-) |
kV |
140/140 |
Impulse puncture test voltage in air |
kV |
302...332 |
Radio interference voltage at 60 GHz |
kV |
10 |
Radio interference voltage at 1000 kHz |
uะ |
50 |
Weight |
kg |
7.9 |
|
All technical requirements and testing are in accordance with IEC standards. |