| Technical Specifications |
| Insulator type |
ANSI |
52-3 |
52-3 |
| Minimum mechanical failing load |
kN |
70 |
100 |
| Minimum mechanical residual strength |
kN |
56 |
60 |
| Testing single impact force |
ะยทะผ |
45 |
| Diameter of the insulating part, D |
mm |
255 |
| Spacing, H |
mm |
146 |
| Nominal creepage distance |
mm |
320 |
| Ball and socket coupling, d (IEC 60120) |
- |
type ะ |
| Puncture voltage in insulating medium |
kV |
130 |
| 50 Hz withstand voltage (dry) |
kV |
80 |
| 50 Hz withstand voltage (wet) |
kV |
50 |
| Impulse puncture test voltage in air |
kV |
280...310 |
| Radio interference voltage at 60 GHz |
kV |
10 |
| Radio interference voltage at 1000 kHz |
uะ |
50 |
| Weight |
kg |
3,6 |
|
| All technical requirements and testing are in accordance with IEC standards. |