Technical Specifications |
Insulator type |
ANSI |
52-5 |
52-5 |
Minimum mechanical failing load |
kN |
120 |
136 |
Minimum mechanical residual strength |
kN |
72 |
81.6 |
Testing single impact force |
ะยทะผ |
45 |
Diameter of the insulating part, D |
mm |
255 |
Spacing, H |
mm |
146 |
Nominal creepage distance |
mm |
320 |
Ball and socket coupling, d (IEC 60120) |
- |
type J |
Puncture voltage in insulating medium |
kV |
130 |
50 Hz withstand voltage (dry) |
kV |
80 |
50 Hz withstand voltage (wet) |
kV |
50 |
Impulse puncture test voltage in air |
kV |
280...310 |
Radio interference voltage at 60 GHz |
kV |
10 |
Radio interference voltage at 1000 kHz |
uะ |
50 |
Weight |
kg |
4.0 |
|
All technical requirements and testing are in accordance with IEC standards. |