| Technical Specifications |
| Insulator type |
ANSI |
52-8 |
52-8 |
| Minimum mechanical failing load |
kN |
160 |
180 |
| Minimum mechanical residual strength |
kN |
96 |
108 |
| Testing single impact force |
ะยทะผ |
45 |
| Diameter of the insulating part, D |
mm |
280 |
| Spacing, H |
mm |
146 |
| Nominal creepage distance |
mm |
385 |
| Ball and socket coupling, d (IEC 60120) |
- |
type K |
| Puncture voltage in insulating medium |
kV |
130 |
| 50 Hz withstand voltage (dry) |
kV |
80 |
| 50 Hz withstand voltage (wet) |
kV |
50 |
| Impulse puncture test voltage in air |
kV |
310...340 |
| Radio interference voltage at 60 GHz |
kV |
10 |
| Radio interference voltage at 1000 kHz |
uะ |
50 |
| Weight |
kg |
6.18 |
|
| All technical requirements and testing are in accordance with IEC standards. |