Technical Specifications |
Insulator type |
IEC |
|
U20BP |
GOST |
PSV120B |
PSV120B |
Minimum mechanical failing load |
kN |
120 |
Minimum mechanical residual strength |
kN |
96 |
Diameter of the insulating part, D |
mm |
280 |
Spacing, H |
mm |
127 |
146 |
Nominal creepage distance |
mm |
445 |
Ball and socket coupling, d (IEC 60120) |
mm |
16 |
Puncture voltage in insulating medium |
kV |
130 |
50 Hz withstand voltage (dry) |
kV |
82 |
50 Hz withstand voltage (wet) |
kV |
50 |
Dry lightning impulse withstand voltage 1.2/50 (+/-) |
kV |
125/125 |
Impulse puncture test voltage in air |
kV |
350...385 |
Radio interference voltage at 0.5 MHz |
dB |
60 |
kV |
20 |
dB |
86 |
kV |
30 |
Weight |
kg |
5.66 |
|
All technical requirements and testing are in accordance with IEC standards. |