Technical Specifications |
Insulator type |
IEC |
U70C |
Minimum mechanical failing load |
kN |
70 |
Minimum mechanical residual strength |
kN |
56 |
Diameter of the insulating part, D |
mm |
255 |
Spacing, H |
mm |
146 |
Nominal creepage distance |
mm |
320 |
Ball and socket coupling, d (IEC 60120) |
mm |
16C |
Puncture voltage in insulating medium |
kV |
130 |
50 Hz withstand voltage (dry) |
kV |
70 |
50 Hz withstand voltage (wet) |
kV |
45 |
Витримувана імпульсна напруга 1,2/50 +/- |
kV |
105/105 |
Impulse puncture test voltage in air |
kV |
280...310 |
Radio interference voltage at 0.5 MHz |
dB |
60 |
kV |
20 |
dB |
86 |
kV |
25 |
Weight |
kg |
38 |
|
All technical requirements and testing are in accordance with IEC standards. |